C640 Models, 22 kW PSU
Input VDC Input VAC Output VDC
320-640 VDC 450-800 VDC 3 x 400 VAC 3 x 480 VAC Output Minimum Maximum
(320-460) (400-530) Current
C 6479 G C 6479 K C 6489 V C 6499 V 360 A 45 55
C 6476 G C 6476 K C 6486 V C 6496 V 320 A 58 68
C 6477 G C 6477 K C 6487 V C 6497 V 170 A 100 130
C 6477 GJ C 6477 KJ C 6487 VJ C 6497 VJ 110 A 190 200
C 6478 G C 6478 K C 6488 V C 6498 V 88 A 200 250
C 6478 GJ C 6478 KJ C 6488 VJ C 6498 VJ 55 A 380 400
C 6477 GH C 6477 KH C 6487 VH C 6497 VH 36 A 570 600
C 6478 GH C 6478 KH C 6488 VH C 6498 VH 27 A 760 800
High Power Density
45-800 Volts Output
19” Rack Mounting
Parallel Redundant Operation
Temperature Controlled Fans
Specification
Input
Input Voltage 320-800 VDC or 400/480 VAC
Input Frequency 47-440 Hz
Output
Output Voltage Up to 800 VDC
Output Current Up to 360 A
Output Power Up to 22 kW
Line Regulation 0.1%(±10%)
Load Regulation 0.2%(10-90%)
Ripple & Noise 0.5% rms
Overload Protection Current limited to 105%-110% of full load
Overvoltage Protecton OVP switches off module with automatic
return to operation
Remote Sense Up to 3 V per wire
General
Efficiency 90% typical
Input/Output Input to Output 3500 VDC
Isolation Voltage Input to Earth 3500 VDC
Output to Earth 3500 VDC
Output to Earth <60-700 VDC
<60-250 V - 2100 VDC
>250 V - 3500 V DC
Connector Terminals/copper bars
Dimensions 8U x 19” x 600mm (355 x 483 x 600 mm)
Weight 90 kg
Environmental
Operating Temperature -10 °C to +50 °C
Storage Temperature -40 °C to +85 °C
EMC & Safety
Emissions EN55022, Class A
EFT/Burst EN61000-4-4 Level 3
Surges EN61000-4-5 Level 3
Safety EN60950, Class 1
Notes:
1. For input voltage <400 VDC output power available reduces by 20%.
Options
Inrush current limiting
Input polarity protection for DC input
Output decoupling diode for redundant/parallel operation
(depending on output current)
Active current sharing for parallel operation
Remote ON/OFF (inhibit)
Monitoring of input and output voltage
Output programmable via analogue signal
RS232 or IEEE488 interface
Automatic/manual selection of charging voltage
Digital V- and A- meter
Tropical protection