www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Specification
1.5-6.0 kVA
• True On-Line UPS
• Complete UPS Cabinet
• Single / Dual Mains Input Option
• Internal Maintenance Bypass Switch Option
• LCD Load Segment Control 2.5 kVA & 3.0 kVA
• Optional 10 Year Batteries
XC Series
Input
Input Voltage (full load • 115 VAC version, 80-138 V
without using battery) 208 VAC version, 176-276 V
230 VAC version, 176-276 V
Input Frequency • 46-64 Hz
Input Power Factor • <0.98 at full load
Input Protection • Fuse/Breaker
Output
Output Voltage • 115 VAC nominal -
100/110/115/120 VAC selectable
208 VAC nominal -
208/220/230/240 VAC selectable
230 VAC nominal -
208/220/230/240 VAC selectable
Output Regulation • ±2% of nominal
Output Waveform • Sine wave
Output THD • <3%, linear load
Crest Factor • 3:1
Output Protection • Electronic overload protection
(ultimately by fuse/breaker)
Efficiency (AC-AC) • 86% up to 1.5 kVA, 90% up to 6.0 kVA
Overload Capacity • See Xi Datasheet
Output Frequency • 50/60 Hz dependent on input
Battery
Internal Battery Type • VRLA 5 year design life standard,
10 year design life option available
Battery Replacement • Hot-swap all models
Recharge • <4 hours to 90%, standard battery only
Battery String Voltage • 48 VDC: 1.5 kVA
96 VDC: 2.5-3.0 kVA
192 VDC: 4.0-6.0 kVA
Autonomy • See Xi Datasheet
Temperature • Autonomy, recharge and battery life
based on +25 ºC ambient
1
General
Input/Output Terminals • Suitable for cable up to 10 mm
2
Display/Alarm • Front panel LCD menu driven, audible
alarms. See System Layout
Interface • VFC Standard (AS400) providing remote
indication of: UPS AC Input OK/ UPS AC
Input
Failure • Battery OK/ Battery Low UPS OK/
UPS Alarm On Inverter /UPS Bypassed
RS232 or USB option available
REPO • Remote emergency power off, must be
fitted for unit to function. Remove link to
shut down output in AC mode or shut
down unit in battery mode
Mechanical (h x w x d) • Small - 1200 mm x 600 mm x 800 mm
Medium - 1700 mm x 600mm x 800 mm
Large - 2100 mm x 600 mm x 800 mm
Bottom entry as standard
Front & rear lockable access
(standard system requires rear access)
Environmental
Operating Temperature • 0 ºC to +40 ºC
Storage Temperature • -15 ºC to +50 ºC
Cooling • Fan assisted cooling fitted to all cabinets
as standard
Operating Humidity • 0-95% RH, non-condensing
Operating Altitude • 3000 metres without derating
Acoustic Noise • <45 dBA at 1 metre
Ingress Protection • Options from IP21 - IP54
EMC & Safety
Emissions • EN55022 level B,
EN50091-2, level B, FCC Class B
ESD Immunity • EN61000-4-2, level 3
Radiated Immunity • EN61000-4-3, level 2
EFT/Burst • EN61000-4-4, level 2
Surge • EN61000-4-5, level 3
Safety Approvals • EN50091-1-1, EN60240-1-1, EN60950, CE
UPS CABINET