Powersolve Electronics Ltd. Unit 8A, Arnhem Road, Newbury. RG14 5RU. United Kingdom p.2/4 12.12D
Phone 0044(0)1635 521858
-
Fax 0044(0)1635 523771
– www.powersolve.co.uk
– [email protected] (Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
Technical Table
Peak Current
Limiting ±6%
R.M.S Current
Limiting ±6%
Allowed Capacitive
Load (max.)
Limiting Time
(T
on
Power On)
Release Time
(T
off
Low Voltage)
Limiting Interval
[T
interval
for AC
cont.
)
Smallest advisable
Circuit Breaker
at 30°C
165A for 20ms / 800A for 200us (even while switching internal bypass relay)
19mA constant at continous operation
Thermal fuse protects overload & fire
Ambient temperature -40°C...+70°C continuous / +75°C short time
-40°C...+85°C for 2 years
IEC/EN60950-1 in accordance with cUL60950
300.000h (IEC/EN61709, Siemens SN29500)
384.000h (+30°C) (IEC/EN61709, Siemens SN29500)
95% (+25°C) not condensing
thermal environment 3K3, mechanics 3M4 (IEC/EN60721)
4000m (13123 ft.) above sea level
UL94V-0 ABS IP20 DIN/EN43880 universal housing for DIN/VDE0603 cutout box and for wall mount
DIN-Rail TS35mm DIN/EN60715 (TS35/7,5 und TS35/15)
Spring-type terminal with cable protection 0,5...6mm² 21…10AWG according with IEC/EN60664-1, IEC/EN61984
General Description:
The CAMTEC ESB101-series are the 2nd generation and cost effective inrush current limiters. The limiters are made for
115/230Vac 16A networks. The line frequency range is 16⅓Hz – 440Hz. The ESB101-Limiter shall be located between the
line-switcher/contactor and the load (p.2/Fig.1). The ESB-models are designed for inductive and capacitive loads. In the
moment of switching-on the system the inrush current of the installed load will be limited for the defined time T
on
(p.4/Fig.5). Independent from the previous inrush level; the current limiting is always strict. After T
on
elapses the current
limiting circuit of the ESB101 will be bypassed. Then the load is directly connected to the AC. The electrical network can
be stressed with current loads as normal (e.g. motors, pumps). If an AC dump overshoots the defined time T
off
, it will be
detected by the ESB101 (p.4/Fig.6). As soon as the AC recovers the inrush will be limited, again (p.2/Fig.3 & 4). The
ESB101-models provide an internal temperature control. In case of a failure the device shuts down to safely prevent
from overheating or burning.